Project Highlights
Hodess Construction served as the design builder for Millipore Corporation’s Mobius II Cleanroom Expansion. Hodess teamed with design firm HL Turner from Concord, NH and RDK Engineers of Andover, MA to design and build a LEED certified cleanroom manufacturing facility. Mobius II is built inside an existing building in Danvers, MA. HCC isolated the construction areas and demolished the interior of the building to create 4,800sf of warehousing, 3,200sf of parts storage and 10,000sf of cleanroom. HCC provided a turnkey installation. From demolition to final certification of the cleanroom, Hodess was responsible for management of all phases of the construction.
Hodess provided design and installation of new mechanical systems to service the cleanrooms while existing systems were reconfigured to service the warehouse and stockroom areas. Highlights of the new systems included the design, installation and fabrication of a 3,200sf structural steel platform approximately 8’ off the roof connected through the roof to the existing pre-cast concrete one story structure.
The new mechanical systems included (2) 100-ton air cooled chillers, (2) 25,000cfm recirculation units for the cleanroom and (1) 9,000cfm make up air unit. The new mechanical systems included highlights such as direct drive in-line fans to reduce maintenance, particulates and service requirements. Duplicate dual fans were installed in the make up unit to provide complete redundancy should one fan fail. All equipment for the new rooms were put on an emergency generator supplied as part of the project.
The system was designed to provide redundancy as well as tight temperature control and humidity control. The cleanroom is controllable to +/- 2º of the set point between 65 and 75º at relative humidity of 45 +/- 5% RH. HCC also provide particle counters in the cleanroom to read the return air stream particulate level. The counters are tied into the control system to drive the speed of the recirculation of fans. Allowing Millipore to reduce the fan speed and increase energy savings during off hours and slow work times when the rooms are especially clean and to increase the air flow to maintain the cleanliness levels required by their products when the rooms are heavily used.
Integrated into the construction, HCC installed (2) large vertical storage units that allow for passing of materials from the dirty stock area through into the cleanroom. The units are pressurized using HEPA filtered air and are interlocked to allow the passage of material and maximize storage.
The cleanrooms were constructed using seamless sheet vinyl floors, 1-1/2 aluminum T-bar cleanroom ceilings with vinyl faced cleanroom tile and the perimeter walls were constructed of 1-hour fire rated drywall to the underside of the roof. The return chases were installed using metal studs and modular laminate cleanroom panels.
The project was done in multiple phases to allow Millipore to maintain the Mobius I production during the construction. Because of the lack of storage on site HCC had to do the asbestos removal and demolition in multiple phases such that materials could be stocked in some of the construction areas until the warehouse area demolition and reconstruction was completed at the beginning of the project. HCC started design in April of 2008 and completed the project January 1, 2009. The month of January was used for certification, validation, and commissioning of the project all of which Hodess managed.
This project was the second project completed for Millipore in Danvers along with the Mobius I project which allowed Millipore to consolidate their manufacturing and increase their output. HCC suggested, created and built a large conference room on one end of the cleanroom. A full height butt glazed glass wall allows for potential customers to meet in the conference room and witness the manufacturing of materials that the customers buy from Millipore. This helps eliminate the need for disruptions in the clean manufacturing space for visits by vendors and customers while still giving the ability to witness and validate the production of the goods supplied to them by Millipore.
The project was completed both on time and under budget and with no accidents or lost time injuries.
Check out Hodess in High-Profile Magazine found on Page 40.
Hodess Construction Completes Millipore Exp.
Similar Hodess Projects
- Hodess Construction Completes 18,000s/f Mobius II LEED certified cleanroom expansion for Millipore Corporation
- Hodess' Cleanroom at GE Healthcare Achieves LEED Gold Certification
- Hodess Construction in Building & Construction Magazine (Northeast) for GE Healthcare
- Hodess Construction to Complete Cleanroom for University of Maryland
- Hodess Awarded Design/Build Cleanroom and Laboratories for Collagen Matrix in Oakland, NJ
- Johnson Controls Inc. - Saft- Lithium Ion Battery Plant, Holland, MI
- Hodess Construction in Building and Construction Northeast for a Second Time.
- Hodess Construction Completes Project for Hovione
- Hodess Construction to Complete Second Job for Insight Technology
- Hodess Construction Corp. awarded Community Tissue Services in Kettering, Ohio
- Hodess Construction to Speak at 2010 Battery Expo in San Jose, CA
- Grand Opening of Saft's Lithium Ion Battery factory in Jacksonville, FL, built by Hodess Construction Corp.
- Hodess' Millipore Mobius II Cleanroom Achieves LEED Gold Certification
- Hodess Cleanroom in GE's Commercial for General Electric Ecomagination.